TC06-10TEH/01,100W DC48V Peltier Thermoelectric Cooler For Outdoor Telecom Cabinet/ Room

Place of Origin : China
Brand Name : ESTEL
Certification : ISO9001:2008
Model Number : TC06-10TEH/01
MOQ : 1 Set
Packaging Details : Wooden Case
Delivery Time : 10~15 Days
Payment Terms : T/T
Supply Ability : 80000 Sets Per Year
Contact Now

100W TEC Air Conditioner

1.Description
The TEC air conditioner is a full automation temperature control device. It uses intelligent controller to control the whole system of the air conditioner. According to the variation of environment temperature, the intelligent controller can automatically detect and operate . The product is widely applied in telecom cabinet, small and medium sized telecom room, UPS room, outdoor base station room, etc. The TEC air conditioner includes the following specs: 100W, 200W, 250W, 350W, 400W, etc. In addition, it also can be custom made.
2. Technical Specs
2.1 General Description
The TEC air conditioner consists of 6 parts: peltier module (including sealing and insulation material), cold end radiator, hot end radiator, cold end fan, hot end fan, monitoring module. When power supply is connected to the TEC, one side of the peltier conduct cooling, and the other side of the peltier conduct heating, the cool (heat) from which will diffuse to the surrounding environment through cold (hot) end radiators and fans. The cold end radiator and cod end fan constitute the inside circulation for cooling the cabinet internal environment, while the hot end radiator and hot end fan constitute outside circulation for heat radiation to the external environment.
Picture 1: TC06-10TEH/01 structure (top view)
Both the inside circulation and outside circulation air ducts adopt air inlet through middle fans and air outlet through radiators at the two sides.
Diagram 1: TC06-10TEH/01 inside circulation and outside circulation air ventilation
2.2 System Parameters

Model No.

TC06-10TEH/01

Cooling Method

air to air

Cooling Object

air

Cooling Object Contact Medium

air

Cooling Effective Power

100W

Heating Effective Power

150W

System Operating Input Voltage

DC48V (43V~58V)

Cooling Stable Current

4.5A±10%

Operating Environmental Temperature

-20°C-55°C

Storage Working Temperature

-50°C-70°C

overheat protection

Can be set

Protection Grade

IP55

Installation Mode

side

Noise

55dB

Service Life

over 7 years

Size (LxWxH)

281x185x180mm

Weight

5Kg


2.3 Dimension


Diagram 2: TC06-10TEH/01 dimension


3. Control
3.1 Application
TC06-10TEH/01 air conditioner uses a common intelligent controller ET724, which is controlled by highly integrated STC single chip microcomputer. The controller, with good performance, easy and convenient installation and set, is widely applied in small and medium sized telecom room, UPS room, outdoor base station room, etc.
3.2 Technical Parameter
(1)Three digit seven segment digital tube displays measured temperature and set temperature.
(2)Temperature measurement accuracy: 0.1 °C ; display accuracy:0.1 °C.
(3)Intelligently choose cooling mode or heating mode.
(4)With protective straight ventilation function.
(5)Power Supply: DC48V.
(6)Power Consumption: ≤5W.
(7)Working environment: -30°C~70°C; <90%RH.
(8)Installation method: guide rail,hanging.
3.3 Control board diagram
Diagram 3: control board diagram
Parameters

Parameter No.

Parameter Name

Initial Value

Remark

P00

FSV


current feedback value, unit: A

P01

Fr1


fan rotating speed 1, per second

P02

Fr2


fan ro


tating speed 2, per second

P03

LOC

0

password parameter, LOC=55, accessible to the following parameters

P04

colTa

25.0

cooling start temperature

P05

colTb

2.0

cooling control return difference

P06

hotTa

15.0

heating start temperature

P07

hotTb

2.0

Heating control return difference

P08

ZFanTa

35.0

straight ventilation start temperature

P09

ZFanTb

2.0

straight ventilation control return difference

P10

tecAL

2.0

TEC current lower limit

P11

tecAH

8.0

TEC current upper limit

P12

TAL

10.0

internal temperature alarm lower limit

P13

TAH

32.0

internal temperature alarm upper limit

P14

BT

0.0

temperature deviation correction

P15

fanEN

0

allow fan fault judgement

P16

tecEN

1

allow TEC fault judgement

P17

ADR

1

communication address

P18

BAUD

2

baud rate:0~3, (2400~19200BPS)

P19

inOH

100

internal fan rotating speed limit

P20

outOH

100

external fan rotating speed limit


4. Mainboard Wiring Diagram
Diagram 4: mainboard interface diagram
J1: keyboard;
J2: temperature sensor input,1 - 5V, 2 - T, 3 - GND;
J3: Prog;
JD1: DC48V input, 1- 48V+, 2 - 48V- ;
JD2: internal and external fans power supply, 1 - +48V, 2 - 0V;
JD3: TEC air conditioner power supply;
When cooling,1 - +48V, 2 - 0V; When heating, 1 - 0V, 2 - 48V;
JD4: straight ventilation output, 1 - +48V, 2 - 0V;
JD5: 1, 2 - system alarm output (dry contact, closure alarm);
3, 4 - temperature alarm output( dry contact, closure alarm);
JD6: fans control interface:
Internal fan control, 1 - Yellow (control output), 2 - White (feedback input);
External fan control, 3—Yellow (control output), 4 -White(feedback input);
JD7: RS485 communication interface:
1 - B-, 2 - A+,3 - SGND.
5. Mainboard Wiring Picture

China Customized Inflatable Bumper Ball Game Bubble Adult Grass CE supplier

TC06-10TEH/01,100W DC48V Peltier Thermoelectric Cooler For Outdoor Telecom Cabinet/ Room Images

Inquiry Cart 0
Send your message to this supplier
 
From:
Enter your email please.
To: TIANJIN ESTEL ELECTRONIC SCIENCE AND TECHNOLOGY CO., LTD
Subject:
Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0